PC-3000XC Controller

PC-3000XC Controller

The PC-3000XC controller is designed to operate up to 3 pumps in pump up or pump down applications. The controllers sequence pumps ON and OFF in response to a change in level input. The easy-to-read blue OLED display provides the operating status, featuring fast and intuitive menu navigation and setup. The PC-3000XC provides for advanced communication functionality for integration to open architecture telemetry/SCADA systems.

Communication
  • RS-485 terminal connections
  • Modbus RTU protocol
  • Designed to work with Pump Watch™ Express gateway remote monitoring system (default)
Advanced Communication

Full bidirectional communication SCADA interface and access to Modbus register addresses to include:

  • Configurable node address
  • Configurable baud rate
  • Read/Write access to level set points
  • Remote LEAD Pump selection
  • Remote Pump Start
  • Remote Pump inhibit
  • Pump ETM and cycle counts
  • Alarm counts
  • And more
pc-3000 xc

Features

  • Configurable front panel; no programming software required
  • Red LED indicates an active alarm
  • Green LEDs indicate pumps required
  • Multiple alternation/sequence configurations
  • High visibility blue OLED backlit 64 x 256 pixel display
  • Process/level displayed digitally and via bar graph
  • Communications established indicator
  • Built in pump failure detection
  • Sensor failure detection with backup float switch to activate pump control override timer and alarm
  • User selectable process/level units
  • Level simulation, I/O, and relay output status screens to aid in setup and system troubleshooting
  • Continuous level monitoring, 4-20 mA level sensor input
  • Flow monitoring (volumetric)
  • Modbus communication via RS-485 comm port
  • Station design data

Specifications

Pump Control and Monitoring:

  • Automatic pump alternation: Simplex, Duplex or Triplex
  • Pump alternation selection
  • Pump over temperature monitoring
  • Pump seal fail monitoring
  • Pump run monitoring
  • Pump fail to start monitoring
  • Low-level and high-level alarms
  • Flow monitoring (volumetric): inflow & discharge

System:

  • Pump cycle counter
  • Pump elapsed time meters
  • Alarm counts
  • Level simulation mode
  • Selectable level measure units

Electrical:

  • 24 VDC supply power (19-28 VDC, 325 mA max)
  • Optional battery backup
  • 6 Relay outputs (120 VAC, 3 A max)
  • 4-20mA analog level input, 14-bit resolution
  • 4-20 mA scalable analog level output 12-bit resolution
  • 11 Digital Inputs (12 VDC, 16mA each

Serial Communication Port

  • RS-485 3-wire
  • Modbus RTU protocol
  • Fixed: 1-stop bit, no parity, and 8 data bits
  • Adjustable baud rate: 1200, 2400, 4800, 9600, 19,200, and 38,400
  • Adjustable node address: 1-247

Mechanical:

  • Overall dimensions: 7.2” x 5.3” x 2.0”
  • Screen dimensions: 2.7” diagonal
  • Panel Mount with 4 mounting holes
  • Pluggable terminal blocks
  • Fits legacy PC-3000 installations

Environment:

  • Operating temperature: 0 to 50°C (32 to 122°F)
  • Storage temperature: -20 to 60°C (-4 to 140°F)
  • Relative humidity (RH): 5% to 95% (non-condensing)
  • Indoor rated: for use indoors or mounted inside of an outdoor rated enclosure

Looking for support
or purchase information?

Contact us